All questions related to installations, configurations and maintenance of Advanced Host Monitor (including additional tools such as RMA for Windows, RMA Manager, Web Servie, RCC).
Trying to get the temperature reading out of the SNMP. I've got the right OID (1.3.6.1.4.1.674.10892.1.700.20.1.6.1.3), but everytime I switch off of the box it adds a .0 to the end of it...which, of course, it can't find. If I hex edit the HostList file to remove the .0, it still doesn't work...BUT, if I then go back into the test and click on the "Get current value" button, it returns the correct value. So, this tells me that I have my OID right, but HostMonitor just doesn't want to use it unless it has a ".0".
H'm, you still use version 1.78??
Anyway, its easy to fix this problem. Just disable "Automatically append the single instance sub-identifier (.0)" option. Option located on Miscellaneous page in the Options dialog.